International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
Experimental Investigation and Comparison of Bend Tube Parallel & Counter Flow and Cross Flow Water to Air Heat Exchanger
Dipayan Mondal*, Md. Owal Ikram, Md. Fazla Rabbi, Md. Nawsher Ali Moral
686
Abstract—This present work represents the experimental investigation and comparison among the parallel flow, counter flow and cross flow arrangements. A characteristic of heat exchanger design is the procedure of specifying a design, heat transfer area and press ure drops and checking whether the assumed design satisfies all requirements or not. Here bend tube heat exchanger used for parallel and counter flow arrangements and cross flow heat exchanger was chosen not only for occupying less space and better performance but also for comparing the perf ormances. The primary aim of this design is to obtain a high heat transfer rate without exceeding the allowable pressure drop. The type of design t hat is utilized determines the coefficient of heat transfer and thus has an effect upon the surface area needed to obtain the des ired level of heat exchange. The flow pattern through most heat exchangers is a combination of counter flow, cross flow and parallel flow. But in bend tube heat exchanger, parallel flow and counter flow are considered therefore counter flow is the most effective configuration for minimizing the needed heat transfer surface area. Within the experimental limit
the gain in temperature for parallel flow was to a maximum value of 120C and the maximum logarithmic mean temperature difference (LMTD), efficiency
and effectiveness were found 29.130C, 42.24% and 0.69 respectively. And for counter flow the gain in temperature was to a maximum value of 130C and the maximum logarithmic mean temperature difference (LMTD), efficiency and effectiveness were 29.360C, 48.59%and 0.86 respectively. Again in cross flow heat exchanger the gain in temperature was to a maximum value of 100C and the logarithmic mean temperature difference (LMTD) was found from
34.630C to 8.370C. The efficiency and effectiveness were found to maximum of 23.11% and 0.96 respectively.
Index Terms— Bend Tube, Parallel & Counter flow, Cross flow, Water to air heat exchange, Temperature distribution, Performances measurement
—————————— ——————————
Heat exchanger is an equipment or device built for efficient heat transfer from one medium to another, whether the media are separated by a solid wall so that they never mix, or the media are in direct contact. It transfers heat from a hot fluid to a cold one [1]. In most heat exchangers, heat transfer between fluids takes place through a separating wall or into and out of wall in a transient manner. In many heat exchangers the fluids are separated by a heat transfer surface and ideally they do not mix or leak. Such exchangers are referred to as indirect transfer type heat exchanger and also referred to as surface heat exchanger. The example of such heat exchanger is automobile radiators [1-2]. In a few heat exchangers, the fluids are in direct contact for exchanging heat. In the direct contact heat exchangers, heat transfer takes place between two immiscible fluids such as a gas and a liquid [1-6]. In general if the fluids are immiscible, the separation wall may
————————————————
Author: Dipayan Mondal, Department of Mechanical Engineering, Khulna University of Engineering & Technology (KUET), Khulna-
9203, Bangladesh, dip.kuet@gmail.com
Co- Author: Md. Owal Ikram, Md. Fazla Rabbi, Md. Nawsher Ali Moral , Department of Mechanical Engineering, Khulna University of Engineering & Technology (KUET), Khulna-9203, Bangladesh
be eliminated and the interface between the fluids replaces a heat transfer surface as in a direct contact heat exchanger. A heat exchanger consists of heat elements such as a core of a matrix containing the surface and fluid distribution such as headers manifolds, tank and inlet or outlet nozzle. Usually there are no moving parts in a heat exchanger. However there are exceptions such as a rotary regenerative exchanger, scraped surface heat exchanger [3-9].
Heat exchangers are one of the most critical components in
any liquefaction/refrigeration system. Its effectiveness governs the efficiency of the whole system. The major requirement of these heat exchangers, working in the cryogenic temperature range, is to have high effectiveness [5]. In the recent past, Atrey has shown in his analysis that decrease in heat exchanger effectiveness from 97% to 95% reduces the liquefaction by 12%. The design of heat exchangers, therefore, is very important from the system performance point of view. The design should take various losses, occurring during the exchange of heat and the performance of the heat exchanger is governed by various parameters like mass flow rates, pressures and temperatures of working fluids etc. [16].
The simplest form of heat exchanger is the double-pipe heat exchanger, which consists of a pipe that runs inside another larger pipe. Types of double-pipe heat exchangers vary in the number of tubes used and in the shape of those tubes.
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
687
Concentric tube heat exchangers are the simplest type of
heat exchanger. The transfer of heat occurs between the fluid that flows inside the smaller pipe and the fluid in the space between the two pipes, through the surface of the smaller pipe [4-9].
Many types of heat exchanger have been developed for use at such varied levels of technological sophistication and sizes as steam power plants, chemical processing plants, petrochemical plants, petroleum refineries, and natural gas processing, building heating and air conditioning and so
on. Common appliances containing a heat exchanger
include air conditioners, refrigerators, and space heaters. These devices are also used in chemical processing and power production [1-10]. In parallel flow arrangement, the hot and cold fluids are flows through the same direction but opposite in counter flow arrangement. In cross-flow arrangement, the hot and cold fluids are flows at the right angle to each other. Unlike a rotary heat exchanger, a cross- flow heat exchanger does not exchange humidity and there is no risk of short-circuiting the airstreams [1-2].
Fig.1: Arrangements for (a) Parallel flow; (b) Counter flow and (c) Cross flow.
The following experimental works were done:
“Effect of Flow Arrangement on the Heat Transfer Behaviors of a Microchannel Heat Exchanger” [11] “Influence of Ionic Fluid in Parallel flow in Shell and Tube Heat Exchanger” [12] “Performance evaluation of counter
flow heat exchangers considering the effect of heat in leak
and longitudinal conduction for low-temperature
applications” [13] “Analysis of a Counter Flow Parallel- plate Heat Exchanger” [14] “Thermal performance analysis of cross-flow unmixed-unmixed heat exchanger by the variation of inlet condition of hot fluid” [15]
D Diameter of the small tube (m) Re Reynolds number d Diameter of the large tube (m) Nu Nusselt number Dm Effective diameter (m) Pr Prandalt number m Mass flow rate(Kg/s) F Correction Factor K Thermal conductivity (W/m .0C)
Q Total heat transfer rate (W) Greeks
L Length of heat exchanger (m) Effectiveness of heat exchanger
A Surface area of heat transfer (m2) η Efficiency (%)
C p Specific heat of the fluid (J/kg. 0C) ρ Density of Fluid (kg/m3)
T Temperature (0C)
Tf Film temperature (0C) Subscripts
∆T temperature difference in heat exchanger (0C) h hot water h Convective heat transfer coefficient (W/m2.0C) c cold air
U Overall heat transfer coefficient (W/m2.0C) i inside
ΔTln Logarithmic Mean Temperature Difference (LMTD) 0C o out side
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
688
3.1. Materials used and stepwise construction
In bend tube heat exchanger, firstly Galvanized Iron pipe were cut into small pieces and the copper tube were bended using sand and inserted concentrically into the Galvanized Iron pipe. Then the outer Galvanized Iron pipe was welded with Elbow and T for the bended area. Again for cross flow heat exchanger, copper tube was bended using sand and then the copper tube was placed into the wooden frame. Galvanized Iron pipe was holed by 1.5mm drill bit. Then it was hanged up along the copper tube surrounding the sheet metal with the wooden frame. Gate valve and blower were used to control the mass flow rate of hot water and cold air to the pipe on the both cases. Separate thermocouples are used on both for measuring the hot water and cold air temperatures with the digital meter.
3.2. Design Condition
The design conditions are usually specified for estimating
heat transfer between inside and outside. It was desired to determine the exit temperatures of the fluids for various entrance conditions. Particular set of conditions depends on many factors other than heat transfer aspects- like cost, space requirements, personal opinions of the designer etc.
3.3. Selection of Fluid
In bend tube heat exchanger, two kinds of fluid both of unmixed are used in where the cold fluid, supply air passes throw the galvanized iron pipe and at every point it gains heat. The hot water enters through the cupper pipe of heat exchanger from the hot water tank and at every point it losses heat and finally it leaves the tube at a certain lower temperature [1-10].
Again in cross flow heat exchanger, two kinds of fluid both of unmixed are used in where the cold fluid, supply air passes inside the copper tube and at every point it gains heat. The supply hot water enters the galvanized iron pipe at a certain higher temperature and exit the pipe at a certain lower temperature [1-10].
3.4. Governing Equation
The LMTD is calculated from the expression [7-10];
i e
ln i
The total amount of heat transfer is denoted
by; Q mC p ; Where, m is total mass flow, kg.s-1; C p is the specific heat of the fluid, J.kg-1. 0C -1; ∆T is the
e
The effectiveness is calculated from the following relations; Effectiveness for the parallel flow [1],
temperature difference in heat exchanger, 0C [1].
The overall heat transfer coefficient U is calculated with the
1 exp[(
UA
Cmin
C
)(1 min )]
Cmax
following relations [6]; Q UAln ; Where Q =Total heat transfer (W); U = Overall heat transfer coefficient
(1 min )
Cmax
Effectiveness for counter flow [8],
(W/(m²·0C)); A = Heat transfer surface area (m2); ΔTln = log
1 exp[(
UA )(1 Cmin )]
mean temperature difference (0C).
Cmin
1 ( Cmin ) exp[(
Cmax
UA )(1 Cmin )]
Heat transfer for pulsating flow in a curved pipe was
numerically studied by Guo et al. for fully developed
Cmax
Cmin
Cmax
turbulent flow for the Reynolds number range of 6000 to
18000 [1]. The Nusselt No. is given below;
Nu 0.328 Re0.58 Pr0.4
But now Dittus-Boelter correlation [1] is
Again, for forced convection and flow inside the cylinder, Nusselt number is given by Nu 0.023 Re0.8 Pr0.4 .This equation is called Dittus-Boelter equation which can be used only when Re 10000 [1-10].
used; Nu 0.023 Re0.8 Pr0.4
.The heat transfer
Again for forced convection and flow over the cylinder,
coefficient (h) [6] is calculated from the relation
Nusselt number is given
0.5 2
below; Nu h Dm ; where D
d D
is mean effective
by Nu (0.04 Re
0.06 Re 3 ) Pr0.4
k
diameter of larger pipe.
m i 0
This equation is called Whitaker correlation which can be used only when 40 Re 100000 [1].
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
689
The heat transfer coefficient (h) [6] is calculated
Nu h Di
The LMTD is calculated from the expression [5];
i e
from;
; where, Di=diameter of copper tube.
k ln i
3.5. Design Criteria
e
Design Parameters | Bend tube Heat Exchanger | Cross flow Heat Exchanger |
Small tube Inside& Outside diameters (Material: copper tube) | Di 0.0127m & D0 0.014m | Di 0.0127m & D0 0.014m |
Large tube Inside& Outside diameters (Material: GI pipe) | di 0.0381m & d 0 0.045m | di 0.0381m & d 0 0.045m |
Hot water & cold air mass flow rate | mh 0.027kg / s & mc 0.024kg / s | mh 0.027kg / s & mc 0.00564kg / s |
Inlet and outlet temp. of hot water | Th1 800 C & Th2 600 C | Th1 800 C & Th2 650 C |
Inlet and outlet temp. of cold air | Tc1 270 C & Tc2 400 C | Tc1 300 C & Tc2 400 C |
Number of holes on the GI pipe | 3 Row each of 18 holes and Diameter of the each hole 0.0015m |
For Bend tube Heat Exchanger: On the basis of the film
4m
u 4 m
12 d 2
4 0.027
12 979.77 0.00152
1.27m / s 2
temperature of water; Re
h
Di
6562.45
R u Dc
1.27 0.013
Dittus-Boelter correlation; Nu 0.023 Re0.8 Pr0.4 37.56 &
h D
& e
39216.15
0.421 10 6
2
Nu 0.04 Re0.5 0.06R
Pr
Nu i
k
i ; and then find hi 1986.61w / m2 .0 C
Whitaker correlation;
3 0.4 &
Again for cold air; Dm di D0 0.0241m and then
Re c 63556.56
Dm
h Di
Nu i
k
; and then find hi 76580.02w / m2 .0 C
4mc
Dittus-Boelter correlation; Nu 0.023 Re0.8 Pr0.4 139.29 &
Again for cold air; Re
Di
30594.85
h D
0.8
0.4
Nu 0 m
; and then find ho 154.49w / m2 .0 C
Dittus-Boelter correlation; Nu 0.023 Re Pr
80.49 &
k
Now, U
1 142.30w / m 2 .0 C &
Nu 0
Now,
Di
k
; and then find ho 160.98w / m
1
2 .0 C
U 154.48w / m 2 .0 C &
D0 1 1
1
1
Di
hi
h0
hi
h0
36.39 C
i e 37.44 0 C
ln i
i
e
ln
Again, Q mh C ph (Th1 Th2 ) 2262.789w and using
e
Again, Q mh C
ph (Th1
Th2
) 1697.09w and using
Correction factor, F 0.96 with the help
Correction factor, F 0.96 with the help
of Q FAUln F (D0 L)Uln it is found L Ls 10.35m
of Q FAU
F (D L)U
it is found L 7.51m ; A
ln c ln
For Cross flow Heat Exchanger: On the basis of film temperature of water; if drill bit diameter is d then,
suction type air blower was used for the both cases having capacity 1hp,5200rpm
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
690
Fig. 2. Schematic diagram (a) for parallel flow; (b) for counter flow (water flow direction is reversed of fig. a); (c) for cross flow heat exchanger.
Under the steady condition, data were collected and recorded and hence the mass flow rate of hot water was varied and the mass flow rate of cold air was fixed.
Fig.3: Temperature distribution curves for parallel flow for (a) observation 1 to 2; (b) observation 3 to 5; (c) observation 6 to 8.
From the above representation for parallel flow, it is observed that the temperature of hot water was varied from 750C to 490C and the cold air temperature was varied from 290C to 270C and it was also observed to pass total length, the hot water temperature was decreased from 580C to 380C and the air temperature was increased from 410C to 370C.
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
691
Fig. 4: Temperature distribution curves for counter flow for (a) observation 1 to 2; (b) observation 3 to 5; (c) observation 6 to 8.
Fig. 5: Temperature distribution curves of related work for counter flow
[14].
Again for counter flow from the above figure, it is observed that the temperature of hot water was varied from 740C to
490C and the cold air temperature was varied from 290C to
270C and it was also observed to pass total length, the hot water temperature was decreased from 550C to 360C and the air temperature was increased from 350C to
410C.Whatever the nature of temperature profiles almost
same both of this project and the referenced work.
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
692
Fig. 6. (a to g)Temperature distribution curve for observation 1 to 7
From the representation for cross flow arrangements, it is
observed that during flow the temperature of hot water was varied from 750C to 480C and the cold air temperature
was varied from 300C to 280C and it was also observed that
to pass the entire length of copper tube, the hot water
temperature was decreased from 650C to 370C and air temperature was increased from 330C to 380C.
Presentation of result for parallel flow, counter flow and for cross flow arrangements remaining constant mass flow rate of cold
air, mc=0.0238 kg/s and mc=0.01 kg/s respectively for bend tube and cross flow heat exchanger.
Fig.7: Performance curves for (a) parallel flow; (b) counter flow (c) cross flow arrangements.
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
693
From the above graphical representation for parallel flow,
the mass flow rate of hot water varied from 0.0138 kg/sec to
0.0061 kg/sec and the measured effectiveness was varied
from 0.69 to 0.51; LMTD was varied from 29.130C to 6.790C; efficiency was varied from 42.24% to 31.53%. Whereas for counter flow, the mass flow rate of hot water varied from
0.0124 kg/sec to 0.0060 kg/sec and the measured effectiveness was varied from 0.86 to 0.74; the LMTD was
varied from 29.360C to 11.320C, efficiency was varied from
48.59% to 42%. Again for cross flow arrangement, the mass flow rate of hot water varied from 0.012 kg/sec to 0.0061 kg/sec and mass flow rate of cold air kept constant at 0.01 kg/sec and it is observed that the calculated LMTD was varied from 34.630C to 10.870C, efficiency was varied from
18.95% to 13.6% and effectiveness was varied from 0.96 to
0.86.
Fig.8: Comparison of the performances among the parallel flow, counter flow and cross flow arrangements.
From the above cure it is concluded that the observed LMTD, efficiency and the effectiveness were maximum for the counter flow arrangement for the desired heat exchanger.
(a)
(b)
Fig.9: Comparison the Relationship between the heat flux and the mass flow rates (a) for this work and (b) for the referenced work [11].
It is seen that the heat flux increases with the increase of mass flow rate. In our project the heat flux is measured more for the counter flow than the parallel flow arrangements. These are the almost same character of the related work.
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
(a) Our Work (b) Related Work [15] Fig.10: A comparable relationship for cross flow arrangement between our work and the related work [15].
694
From the above fig.10, it is seen that not only the efficiency
but also the heat transfer rate are increased with the increase of the mass flow rate of hot fluid but a reverse direction was found at first on the both of efficiency and heat transfer rate analysis. The initially decreasing phenomena are measured in our work but the decreasing phenomena at last segment were measured at the related work.
It is concluded that not only in parallel flow but also in counter flow the temperature of hot water was decreased with distance almost uniformly and the temperature of cold air was increased with distance. But the difference between the parallel and counter flow characteristics was that the temperature difference was more rapid and effectiveness is also greater in counter flow than that of parallel flow. Again it is found from the competitive study the counter
flow arrangement also gives the greater temperature
difference; heat flux and the effectiveness than that of cross
flow arrangement.
The designed value that was assumed was not obtained during experiment. It was deviated. The mass flow rate of hot water was not maintained as the assumed value due to the low head tank. The mass flow rate of air was obtained by calibrating with previous data which was not maintained as the assumed value. In the bend tube heat exchanger the hot water is passed through the copper pipe which was not always maintained the concentric with Galvanized iron pipe and for the cross flow arrangement the hot water was flow over the copper tube from the galvanized iron pipe which was not contacted all the portion of the copper tube due to the alignment problem. So the temperature difference was not obtained as the assumed value. And the result of this experiment was
fluctuated from the design result.
On the basis of the experimental the gain in temperature for parallel flow was to a maximum value of 120C, for water flow rate of 0.0128 kg/sec and air flow rate of 0.0238 kg/sec. Within the experimental limit the gain in temperature for counter flow was to a maximum value of 130C, for water flow rate of 0.0077 kg/sec and air flow rate of 0.0238 kg/sec. Within the experimental limit LMTD was found from 150C
to 300C.The efficiency and the effectiveness were found to a
maximum value of 48.59% and 0.86 respectively. Again for cross flow arrangement, the gain in temperature was to a maximum value of 100C, for water flow rate of 0.014 kg/sec and air flow rate of 0.01 kg/sec. Within the experimental limit LMTD was found from 34.630C to 8.370C.The efficiency, effectiveness and the LMTD were found to a maximum value of 23.11%, 0.96 and 34.630C respectively. Overall heat transfer coefficient was found to a maximum
value 157.67 w/m2. 0C
IJSER © 2014 http://www.ijser.org
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014
ISSN 2229-5518
695
The authors wish to thank Prof. Dr. Md. Nawsher Ali Moral, Department of Mechanical Engineering, Khulna University of Engineering & Technology (KUET) and would also like to gratefully KUET, Bangladesh for the financial support.
[1] Ozisik, M.N; “Heat Transfer, A Basic Approach.” International Edition, 1985; Tata McGraw-Hill Publishing Company Limited; New Delhi W.-K. Chen, Linear Networks and Systems. Belmont, Calif.: Wadsworth, pp. 123-135, 1993. (Book style)
[2] http://1heatexchanger.info/2009/10/what-is-a-heat-
exchanger-2/
[3] http://www.engineersedge.com/heat_transfer/parallel_
counter_flow_designs.htm
[4] http://en.wikipedia.org/wiki/Heat_exchanger/Plate_hea
t_exchanger
[5] Kays, W.M., and A. L. London: Compact Heat
Exchangers, 2nd edition, McGraw-Hill, New York, 1964 [6] http://en.wikipedia.org/wiki/Heat_transfer_coefficient [7] http://en.wikipedia.org/wiki/Log_mean_temperature_d
ifference
[8] http://en.wikipedia.org/wiki/Effectiveness
[9] Nag, P.K; “Heat and Mass Transfer,” Second Edition;
Tata McGraw-Hill Publishing Company Limited; New
Delhi
[10] Holman, J.P; “Heat Transfer”, Ninth Edition, 2004; Tata
McGraw-Hill Publishing Company Limited; New Delhi
[11] Dang Thanhtrung, Teng Jyh-tong, and Chu Jiann-
cherng; “Effect of Flow Arrangement on the Heat
TransferBehaviors of a Microchannel Heat Exchanger”,Proceeding of the International Conference of Engineers & Computer Scientists 2012 Vol III, IMECS 2010,March 17-19, Hon Kong, ISBN: 978-988-
18210-5-8.
[12] N.D.Shirgire1 S.S.Bhansali, Dr. U.V.Kongre, P.S.Ghawade, P.R.Bodade;“Influence of Ionic Fluid in Parallel flow in Shell and Tube Heat Exchanger”, International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May
2013, ISSN: 2319-5967, ISO 9001:2008 Certified
[13] Prabhat Gupta *, M.D. Atrey; “Performance evaluation of counter flow heat exchangers considering the effect of heat in leak and longitudinal conduction for low- temperature applications”, Cryogenics 40 (2000) 469-
474, Cryogenics and Superconductivity Section, Centre
for Advanced Technology (CAT), Indore 452 013, India, Received 4 September 2000; accepted 13 November
2000
[14] Ruoxu Jia, Junling Hu, and Abubaker E.M Elbalsohi; “Analysis of a Counter Flow Parallel-plate Heat Exchanger”, ASEE 2014 Zone I Conference, April 3-5,
2014, University of Bridgeport, Bridgeport, CT, USA. [15] Dr. M K Chopra and Ramjee Singh Prajapati; “Thermal
performance analysis of cross-flow unmixed-unmixed heat exchanger by the variation of inlet condition of hot fluid”, International Refereed Journal of Engineering and Science (IRJES), Volume 3, Issue 1 (January 2014), PP.
29-31, ISSN (Online) 2319-183X.